BackflowNear Test-Due Reminder

City of St. Peters: backflow testing rules

Serves St. Peters, MO. Every point below comes from City of St. Peters's own pages, linked; check your notice for your own deadline.

Who must test

  • An approved RPZ device must be installed on all lawn irrigation and sprinkler systems and on fire systems with chemical additives; an RPZ or double check is required on other fire protection systems. Source.
  • An approved backflow device is required on all potable service lines entering retail, commercial and industrial facilities, including schools, churches and hospitals. Source.

Notices and deadlines

  • Double check and reduced pressure assemblies must be tested at installation and annually by June 1, and overhauled at least every five years. Source.

How the report is filed

  • The DNR certified tester must submit test reports for each device within 30 days of the test and no later than June 1, on a Missouri DNR approved form, fully completed, signed and dated. Source.

Tester registration

  • Inspections, tests and overhauls are at the customer's expense and must be done by a State of Missouri certified backflow prevention device tester. Source.

Fees

  • A $30 late fee per device is charged to the water bill for any test report not received by June 1. Source.

If a test is missed

  • Service is disconnected if a test report is not received within 60 days of the June 1 date, until reports are received and fees paid; test failures must be corrected within 10 working days. Source.
  • Inspection and testing failures must be corrected within ten working days or water service is disconnected until fixed. Source.

Program

  • City code Article VIII governs backflow devices. Source.

Read October 6, 2026. Program page: ecode360.com.

Find a tester Set reminder