Virginia backflow testing rules
12VAC5-590-580 (Virginia Department of Health Waterworks Regulations): the owner documents the program in a written plan and submits it to VDH for approval.
Who sets the rules in Virginia
The owner reviews the program and written plan at least every five years (12VAC5-590-600A).
Sources: Every waterworks owner must run a cross-connection control program; The plan is reviewed at least every five years
Is an annual test required?
Under 12VAC5-590-600E, each program sets procedures for testing assemblies at least once a year and after installation, relocation or repairs.
The waterworks rule also points to the Uniform Statewide Building Code (13VAC5-63-530), which requires reduced pressure, double check and pressure vacuum breaker assemblies to be tested after installation, after repairs or relocation, and every year.
Source: Testable containment assemblies checked at least once a year
Which properties need a backflow preventer
12VAC5-590-610E lists 23 types, including hospitals, mortuaries, clinics, laboratories, car washes and laundries, food and beverage plants, health clubs with pools, highrise buildings of four or more stories, and multiuse commercial, office or warehouse facilities.
Properties with fire protection, lawn sprinkler or irrigation systems need a backflow assembly or elimination method (12VAC5-590-610C(5)).
The hazard table (12VAC5-590-630, Table 630.1) lists lawn irrigation as a high hazard example and home fire sprinklers built of drinking water materials as low hazard.
For single-family homes with irrigation or fire systems, the water system may decide whether to keep an inventory (12VAC5-590-600H).
Sources: Assemblies required at listed facility types; Lawn irrigation is a high hazard example; potable-material residential fire sprinklers are low hazard; Water systems may skip inventories for single-family homes with irrigation or fire systems
Who may do the test
12VAC5-590-630D: since January 1, 2023, people who test or repair backflow assemblies and devices must be certified through the Commonwealth tradesman program (DPOR backflow prevention device workers).
Under Code of Virginia 54.1-1129B, local governments must accept the state's backflow prevention device worker certification as proof of experience and training.
Sources: Testers must hold Virginia's backflow prevention device worker certification; The DPOR certification is voluntary under the statute, but localities must accept it
How the test report is filed
Water systems keep an inventory and records of testing, repairs and maintenance for every assembly (12VAC5-590-600H and I).
Backflow events are reported to the Virginia Department of Health within one business day, with a written report by the 10th of the next month (12VAC5-590-600G).
Source: Water systems keep inventories and test, repair and maintenance records
If a test is missed
Each program must be able to discontinue or refuse service (12VAC5-590-600F) when a consumer does not install, test and maintain a required assembly, removes or bypasses it, or keeps an unprotected cross-connection.
Not testing and maintaining a required assembly is a listed reason for shutoff (12VAC5-590-600F(1)).
Source: Water systems must be able to discontinue or refuse service
Finding a tester
Virginia backflow prevention device workers are certified under DPOR's Tradesmen program; DPOR's License Lookup checks a certification, and DPOR posts a list of approved backflow training schools.
Common questions
Is backflow testing required every year in Virginia?
Yes. Virginia's waterworks rule (12VAC5-590-600E) requires each water system's program to test assemblies at least once a year, and the building code requires reduced pressure, double check and pressure vacuum breaker assemblies to be tested every year.