California backflow testing rules
The Cross-Connection Control Policy Handbook (CCCPH), adopted by the State Water Resources Control Board on December 19, 2023 and amended April 21, 2026, sets the cross-connection rules for California public water systems.
Who sets the rules in California
Compliance with the handbook is mandatory for every California public water system (CCCPH 1.2).
Sources: State Water Board Cross-Connection Control Policy Handbook in force since July 1, 2024; Compliance is mandatory for every public water system
Is an annual test required?
Backflow prevention assemblies must be field tested at least once a year (CCCPH 3.3.3(b)); the water system, the State Water Board or a local health agency may require more frequent tests for high hazard premises.
Assemblies are also tested after installation, repair, depressurizing for winter or relocation (CCCPH 3.3.3(a)).
Assemblies that fail must be repaired or replaced within 30 days of notice of the failure (CCCPH 3.3.3(e)); a water system may allow extensions if its plan provides for them.
Source: Backflow prevention assemblies field tested at least once a year
Which properties need a backflow preventer
High hazard premises need an air gap or a reduced pressure principle assembly. CCCPH Appendix D lists examples, including sewage facilities, mortuaries, medical and dental facilities, laboratories, car washes, hotels and motels, gas stations, agricultural premises and sites with an auxiliary water supply.
Premises with a fire protection system need at least double check protection within ten years of the handbook's effective date, and high hazard fire systems, such as those with chemical additives or an auxiliary supply, need at least a reduced pressure assembly (CCCPH 3.2.2(e)).
A low hazard home fire sprinkler system needs no assembly only if it has one service connection, a split service line, a single meter, NSF/ANSI 61 piping and piping looped to a fixture used routinely (CCCPH 3.2.2(e)(3)).
Homes get hazard assessments, but not necessarily in person: the State Water Board's June 2025 FAQ says water systems may use GIS, building records or customer surveys.
Sources: High hazard premises need an air gap or reduced pressure principle assembly; Residential connections get hazard assessments, but not necessarily in person
Who may do the test
All required field tests must be done by certified backflow prevention assembly testers (CCCPH 3.3.3(a)).
Testers must hold a valid certification from an organization the State Water Board recognizes (CCCPH 3.4.1(a)). From July 1, 2027, only certifications from organizations accredited to ISO/IEC 17024 by ANSI ANAB or a recognized partner count.
Source: All required field tests must be done by certified testers
How the test report is filed
Water systems keep three calendar years of field test results, with the tester's name, test date, repair date and certification number (CCCPH 3.5.1(a)(4)).
Testers must tell the water system within 24 hours if they see a backflow incident or an unprotected cross-connection (CCCPH 3.3.3(f)).
A new assembly needs a passing field test before the water system provides continuous service (CCCPH 3.3.3(d)).
Source: Water systems keep three calendar years of test results with the tester's certificate number
If a test is missed
When a customer does not install, inspect, test or maintain a required assembly, the water system must be able to deny or discontinue service, do the work itself, or otherwise address the failure in a timely manner (CCCPH 3.1.3(a)(1)).
Service is cut off when a backflow incident is confirmed and restored only after a passing field test (CCCPH 3.3.3(f)).
Source: Water systems must have legal power to deny or discontinue service for noncompliance
Finding a tester
Certifying organizations must publish a public website list of their certified testers, with name, certification number and expiry date (CCCPH 3.4.1(b)(5)).
Source: Certifying organizations must publish a public list of their certified testers
Common questions
Is backflow testing required every year in California?
Yes. California's Cross-Connection Control Policy Handbook requires backflow prevention assemblies to be field tested at least once a year, and after installation, repair or relocation.