Oklahoma backflow testing rules
Oklahoma DEQ rule OAC 252:631 (Public Water Supply Operation) applies to any person or entity operating a Public Water Supply system, except minor systems regulated under OAC 252:624.
Who sets the rules in Oklahoma
OAC 252:631-3-17(b)(1) (amended eff 9-15-25): PWS systems shall not allow a physical connection between a drinking water line and a line carrying water of unknown or questionable quality.
OAC 252:631-3-17(b)(2): an air gap of at least 6 inches or two pipe diameters, with a reduced pressure zone backflow device accepted in lieu of an air gap. Fire suppression systems are not treated as hazardous supplies.
Oklahoma's rules (OAC 252:631-3-17(b)(3) and 252:626-5-15(a)(3)) bar any cross-connection between a public water system and a private water system.
The construction standard OAC 252:626-5-15 repeats the cross-connection limits for new water works.
Oklahoma's rules also say backflow prevention devices may not be placed in a pit or vault where they can be submerged.
Sources: OAC 252:631 sets operating standards for public water supply systems; Construction standards (OAC 252:626-5-15) repeat the cross-connection limits for new works
Which properties need a backflow preventer
Under OAC 252:631-3-17(b)(2) and 252:626-5-15(a)(2), a fire suppression system is not considered a hazardous water supply for the air gap or reduced pressure device requirement.
Source: Fire suppression systems are not considered a hazardous water supply
Common questions
Is backflow testing required every year in Oklahoma?
Oklahoma's DEQ rules (OAC 252:631) require an air gap or a reduced pressure device on connections to water of questionable quality but do not set a statewide test interval; each water system sets its own schedule.