Texas backflow testing rules
30 TAC 290.46(i) requires each public water system to adopt an adequate plumbing ordinance, regulations, or service agreement with enforcement provisions preventing cross-connections; the water purveyor runs the local program.
Who sets the rules in Texas
30 TAC 290.44(h)(1): no water connection to any residence or establishment with an actual or potential contamination hazard unless protected.
290.44(h)(1)(A): additional protection at the meter as an air gap or backflow prevention assembly.
30 TAC 290.46(j): CSI required for all new construction, existing connections with suspected hazards, and after material plumbing changes.
Source: Every public water system must adopt a plumbing ordinance, regulations or service agreement
Is an annual test required?
30 TAC 290.44(h)(4): all required assemblies tested on installation; assemblies protecting against health hazards must be tested at least annually.
RG-478 (Feb 2026), whether at the meter or part of an internal program.
RG-478 explains TCEQ requires nonhealth-hazard assemblies to be tested upon installation; local code or ordinance may require annual tests.
Systems' ordinances must be at least as stringent as TCEQ rules and may be stricter.
Source: Tested on installation; health-hazard assemblies tested at least annually by a recognized tester
Which properties need a backflow preventer
Examples of businesses required to install high-grade assemblies and have them tested annually by a certified tester under water system CCC programs.
Landscape irrigation rule reproduced in RG-478: assemblies on irrigation systems designated as health hazards (for example chemical additives, OSSF sites) tested annually; all irrigation assemblies tested after installation.
30 TAC 344.52(c).
30 TAC 290.44(h)(4)(A)(ii) limits who may test and repair assemblies on firelines.
RG-345 (revised Oct 2008) states the purveyor is responsible and cites 290.44(h)(4) annual test for health hazards.
30 TAC 290.44(h)(6): no assembly required at a residence with no actual or potential contamination hazard.
Sources: TCEQ page: mortuaries, surgery centers, hospitals, chemical plants example of annual testing; Irrigation systems designated health hazards must be tested annually (30 TAC 344.50(e)); TCEQ guidance on fire systems: water purveyor ensures backflow requirements are met
Who may do the test
Recognized testers have completed a TCEQ-approved course, passed an exam administered by the executive director and hold a current license.
TCEQ BPAT page: licence required to repair or test backflow prevention assemblies.
From the TCEQ BPAT page.
Sources: Tester must hold a current TCEQ BPAT license; State licence authority: person who tests or repairs assemblies must hold a TCEQ licence
How the test report is filed
30 TAC 290.44(h)(4)(C): signed and dated original submitted to the public water supplier; TCEQ Form 20700. No state day deadline found (local ordinance sets it).
RG-478 says the BPAT forwards the signed original and the PWS retains it at least three years.
Source: Signed test report goes to the public water supplier
If a test is missed
RG-478: PWS may terminate service where an unprotected health hazard is found and restore only when isolated.
RG-478 lists enforcement tools for water suppliers.
Source: Water system may terminate service to unprotected health-hazard connections
Finding a tester
Texas licensed testers are found through TCEQ's online licence search at www2.tceq.texas.gov (robots.txt disallows automated access, not fetched; manual look-up only).
Source: TCEQ BPAT licence page lists the licence search tools (Individual Search, Group Search)
Common questions
Is backflow testing required every year in Texas?
30 TAC 290.44(h)(4): all required assemblies tested on installation; assemblies protecting against health hazards must be tested at least annually.