Texas backflow testing rules
30 TAC 290.46(i) requires each public water system to adopt an adequate plumbing ordinance, regulations, or service agreement with enforcement provisions preventing cross-connections; the water purveyor runs the local program.
Who sets the rules in Texas
30 TAC 290.44(h)(1): no water connection to any residence or establishment with an actual or potential contamination hazard unless protected.
290.44(h)(1)(A): additional protection at the meter as an air gap or backflow prevention assembly.
30 TAC 290.46(j): CSI required for all new construction, existing connections with suspected hazards, and after material plumbing changes.
Source: Every public water system must adopt a plumbing ordinance, regulations or service agreement
Is an annual test required?
30 TAC 290.44(h)(4): all required assemblies tested on installation; assemblies protecting against health hazards must be tested at least annually.
TCEQ's guidance RG-478 (February 2026) says health hazard assemblies must be tested when installed and at least once a year by a licensed tester, whether at the meter or inside the property.
RG-478 explains TCEQ requires nonhealth-hazard assemblies to be tested upon installation; local code or ordinance may require annual tests.
Systems' ordinances must be at least as stringent as TCEQ rules and may be stricter.
Source: Tested on installation; health-hazard assemblies tested at least annually by a recognized tester
Which properties need a backflow preventer
TCEQ names mortuaries, surgery centers, hospitals and chemical plants as examples of businesses that must install high-grade assemblies and have them tested every year by a certified tester.
Under the landscape irrigation rule (30 TAC 344.50(e)), assemblies on irrigation systems designated as health hazards, such as those with chemical additives, are tested every year; all irrigation assemblies are tested after installation.
Under 30 TAC 344.52(c), the irrigator tests the assembly before it goes into service and sends the results to the local water utility within 10 business days.
Under 30 TAC 290.44(h)(4)(A)(ii), testers may test and repair assemblies on fire lines only if they are permanently employed by an Approved Fireline Contractor.
TCEQ guidance RG-345 says the water utility is responsible for making sure fire system backflow requirements are met.
30 TAC 290.44(h)(6): no assembly required at a residence with no actual or potential contamination hazard.
Sources: TCEQ page: mortuaries, surgery centers, hospitals, chemical plants example of annual testing; Irrigation systems designated health hazards must be tested annually (30 TAC 344.50(e)); TCEQ guidance on fire systems: water purveyor ensures backflow requirements are met
Who may do the test
Recognized testers have completed a TCEQ-approved course, passed an exam administered by the executive director and hold a current license.
TCEQ says anyone who tests or repairs backflow prevention assemblies must hold a TCEQ license.
Licensed testers may test and repair assemblies on any domestic, commercial, industrial or irrigation service, according to TCEQ.
Sources: Tester must hold a current TCEQ BPAT license; State licence authority: person who tests or repairs assemblies must hold a TCEQ licence
How the test report is filed
Under 30 TAC 290.44(h)(4)(C), the tester submits the signed and dated original report (TCEQ Form 20700) to the public water supplier. The local ordinance sets the deadline.
RG-478 says the BPAT forwards the signed original and the PWS retains it at least three years.
Source: Signed test report goes to the public water supplier
If a test is missed
RG-478: PWS may terminate service where an unprotected health hazard is found and restore only when isolated.
TCEQ guidance lists fees, due dates, required installation of a backflow preventer and shutoff of water service as examples of enforcement.
Source: Water system may terminate service to unprotected health-hazard connections
Finding a tester
Licensed Texas testers can be looked up in TCEQ's online license search (Individual Search or Group Search).
Source: TCEQ BPAT licence page lists the licence search tools (Individual Search, Group Search)
Common questions
Is backflow testing required every year in Texas?
Yes for health hazard assemblies. Under 30 TAC 290.44(h)(4), assemblies that protect against health hazards must be tested at least once a year; other assemblies are tested at installation, and local ordinances may require yearly tests.
Related site: Own a fire sprinkler system in Texas? The sprinkler inspection rules are separate from the backflow test. Texas fire inspection rules on FireInspectorNear, our sister directory.