BackflowNear Test-Due Reminder

Illinois backflow testing rules

Under 35 Ill. Adm. Code 604.1505(a), every community water supply must run a cross-connection control program.

Sources read October 7, 2026. Each section links the pages it came from.

Who sets the rules in Illinois

The water supply must survey its distribution system for cross-connections at least every three years (35 IAC 604.1505(b)(2)).

The water supply must adopt and enforce an ordinance that meets the Illinois Plumbing Code (35 IAC 604.1505(b)(4)).

Source: All community water supplies must have a cross connection control program

Is an annual test required?

Under 35 IAC 604.1510(a), cross-connection control devices must be inspected at least once a year by an inspector approved by the Illinois EPA, and mechanical devices must be physically tested.

The Illinois Plumbing Code (77 IAC 890.1130(b)) requires assemblies to be tested by a Cross-Connection Control Device Inspector (CCCDI) before first use and at least once a year after.

That annual test covers reduced pressure principle (RPZ), reduced pressure detector, double check and double check detector assemblies (77 IAC 890.1130(b)).

Sources: Cross-connection control devices must be inspected at least annually by an approved inspector; Plumbing Code: RPZ, RPDA, DCA and DCDA assemblies tested before first use and at least annually

Which properties need a backflow preventer

Any lawn sprinkler system connected to drinking water must have an RPZ assembly (77 IAC 890.1140(d)), so home irrigation is covered.

Fire safety systems need backflow protection unless they are small looped systems built of drinking water pipe with no non-potable or fire department connection and 20 or fewer sprinkler heads (77 IAC 890.1130(d)).

Fire systems that contain antifreeze or other chemicals need an RPZ or an air gap (77 IAC 890.1130(d)(3)).

On a lawn sprinkler system the RPZ may sit outdoors if it is protected from freezing or removed at the end of the season (77 IAC 890.1140(d)).

Sources: Lawn sprinkler systems on potable water need an RPZ; Fire safety systems: backflow protection required except small looped potable systems

Who may do the test

Inspectors must be approved by the Illinois EPA as Cross-Connection Control Device Inspectors and be authorized to do plumbing under the Illinois Plumbing License Law (35 IAC 604.1510).

Source: Inspector must be approved by the Illinois EPA (or its designee) as a CCCDI

How the test report is filed

Records of the annual inspection go to the community water supply (35 IAC 604.1510(a)(1)), and each device gets a tag with the test date and the inspector's name.

The water supply keeps records of every backflow preventer that needs annual testing (35 IAC 604.1505(b)(5)).

Sources: Annual inspection records go to the community water supply; Water supply keeps records of all backflow preventers requiring annual testing

If a test is missed

An inspector's approval can be suspended or revoked for falsified reports or willful negligence (35 IAC 604.1510(b)(3)).

Source: CCCDI approval can be suspended or revoked for falsified reports or willful negligence

Common questions

Is backflow testing required every year in Illinois?

Yes. 35 Ill. Adm. Code 604.1510 requires cross-connection control devices to be inspected at least once a year by an Illinois EPA approved inspector, and the Illinois Plumbing Code requires reduced pressure and double check assemblies to be tested every year.

Find a tester Set reminder