Washington backflow testing rules

All community water systems in Washington must meet the cross-connection control requirements of WAC 246-290-490 (Department of Health).

Sources read October 6, 2026. Each section links the pages it came from.

Who sets the rules in Washington

Each water purveyor must develop and run a cross-connection control program (WAC 246-290-490(2)(a)) and may be stricter by local ordinance.

The purveyor's responsibility stops at the consumer's water system; inside the property, the local plumbing authority is responsible (WAC 246-290-490(1)(e)).

Source: All community water systems must meet WAC 246-290-490

Is an annual test required?

Under WAC 246-290-490(7)(b)(ii), assemblies are tested at installation, after repair or relocation, after a backflow incident and every year after; the purveyor may require more often for high hazard premises or repeated failures.

A certified Backflow Assembly Tester (BAT) does the tests (WAC 246-290-490(7)(a)(iii)).

Atmospheric vacuum breakers on irrigation systems are inspected at installation, after a backflow incident and after repair or relocation, rather than tested every year (WAC 246-290-490(7)(c)).

Source: Annual inspection or test of assemblies that protect the public water system

Which properties need a backflow preventer

Table 13 of WAC 246-290-490 lists high hazard premises that need an air gap or reduced pressure assembly at the service, including hospitals and clinics, car washes, laboratories and food plants.

Residential flow-through or combination fire systems built of drinking water pipe need no backflow protection; other fire systems need a double check or, with chemicals or an auxiliary supply, a reduced pressure assembly (WAC 246-290-490(4)(d)).

For a home irrigation system, the purveyor may accept an approved atmospheric vacuum breaker installed under the Uniform Plumbing Code (WAC 246-290-490(4)(c)(ii)).

Source: High hazard premises named: hospitals, car washes, laboratories, food plants and others

Who may do the test

Only a Backflow Assembly Tester certified by the Department of Health under chapter 70A.120 RCW may test (WAC 246-292-010).

Each purveyor's quality assurance program covers tester certification, test kit calibration, test report contents and deadlines for submitting reports (WAC 246-290-490(3)(g)).

Sources: Only a certified BAT (Backflow Assembly Tester) may test under the purveyor program; Purveyor must keep a QA program including BAT certification documentation

How the test report is filed

The tester sends the field test report to the owner of the backflow preventer and to the purveyor (WAC 246-292-034(4)); the purveyor sets the deadline.

The purveyor completes an annual cross-connection control program summary report on Department of Health forms (WAC 246-290-490(8)(d)).

Backflow incidents are reported to the department and local authorities by the end of the next business day (WAC 246-290-490(8)(f)).

Sources: BAT sends the field test report to the device owner and the purveyor; Purveyor completes an annual cross-connection program summary report

If a test is missed

The purveyor may deny or discontinue water service until the hazard is eliminated or controlled (WAC 246-290-490(2)(i)), after notifying the local authority except in an emergency.

Source: Purveyor may deny or discontinue service until the hazard is controlled

Common questions

Is backflow testing required every year in Washington?

Yes. WAC 246-290-490 requires assemblies that protect the public water system to be tested at installation and every year after, and the purveyor may require more often.