Carmel Utilities: backflow testing rules

Serves Carmel, IN. Every point below comes from Carmel Utilities's own pages, linked; check your notice for your own deadline.

Who must test

  • Reduced pressure principle assemblies and pressure vacuum breakers must be tested at intervals not exceeding six months, or annually if installed on an irrigation system. Source.
  • Double check valve assemblies and double check detector assemblies must be tested at intervals not exceeding one year. Source.
  • A backflow prevention device is required on all commercial domestic water service lines, downstream of the meter; fire sprinkler systems need a double check valve assembly, or an RP if chemicals are used. Source.

How the report is filed

  • All backflow device installations must be inspected and tested by a certified tester, with a copy of the test report sent to Carmel Utilities, before domestic or fire service starts. Source.

Tester registration

  • Testers are certified by the State of Indiana after a 35-hour training class, a written exam and hands-on device tests; Carmel Utilities and Aqua Backflow do not test devices. Source.

Fees

  • Backflow replacements require a Backflow Replacement Inspection; a re-inspection due to failure or equipment not ready costs the same as a trip charge (rate not stated). Source.

If a test is missed

  • Failure to have the device tested in a timely manner could result in loss of water service. Source.

Program

  • Carmel's cross-connection control rules are adopted in city ordinance A-69, implementing Title 327 IAC 8 Rule 10. Source.